I have been convinced for years that the National Electrical Code is written first and foremost to serve the interests of electrical wiring device manufacturers, and not the needs of end users, or even the safety of end users.

The way the AFCI mess played out lost them so much credibility that it is hard to take this seriously as being about "safety" any more.




What AFCI mess?


Search online for "AFCI" along with any appliance that has a motor in it, like a vacuum, refrigerator, or hair dryer. You'll get pages of posts of people asking why the appliances keep tripping the AFCI breaker.

The reason why is that those devices create arcs, and AFCI breakers are completely unable to handle them. Some regions require AFCI breakers, so a significant portion of household appliances will occasionally trip the breaker.

The worst part is that it isn't particularly consistent, so your fridge could last for years without tripping it, but as brushes wear the arcs they regularly create increase the chances of a trip, until one day you find that all your food is ruined, because the AFCI breaker tripped at an inopportune time.

Fortunately, my fridge trips the AFCI very reliably, so I was able to detect it before losing any food. All I had to do to fix it was make a few passes with the hot wire through a ferrite bead, right before it connects to the AFCI breaker. It completely blocks the arc-created RF that the AFCI is detecting, disabling the functionality of the AFCI, all without any code violations, because while the AFCI is required, the ferrite bead isn't prohibited.


I upgraded all of my breakers to AFCI+GFCI. Worked flawlessly so far (about 6 months in).

The only two times where my AFCI tripped were 1) my blow-dryer shorted out due to a worn out cable (WAI) and 2) the PSU on my PC started tripping the AFCI (sent back to the manufacturer and got a replacement). So in both cases, at least for me, the AFCIs caught real problems.

Not a single trip of the GFCI function so far including vacuum, fride, and various power tools (and it's great peace of mind to have this with kids in the house).


> 2) the PSU on my PC started tripping the AFCI (sent back to the manufacturer and got a replacement).

That's a common occurrence with an AFCI breaker and a switched mode power supply.

In my last apartment, I had multiple AFCI breakers nuisance trip with multiple PC power supplies, usually when the GPU has heavy usage.

Eventually I "solved" it by getting a double conversion UPS.


All good for the average user. You cannot run a saw or other corded power tool off an AFCI breaker. it trips _constantly_. This is a problem because NEC wants AFCI/GFCI in all rooms with concrete floors, like garages. This means you basically put those plugs in to pass and then pull them out again.


That wasn't a defective PSU, that was your AFCI, tripping from RF that isn't even generated by an arc. The new can still trip at any time.


Basically they mandated hardware that is way more expensive than what it replaces and reliably gets falsely triggered by normal usage that the circuit is supposed to support.


AFCI stands for "Arc Fault Circuit Interrupter", a type of device that detects arcing (sparks) on a circuit and will shut things down if the "arc strength" is above some arbitrary threshold. The main risk from arcing is fire. Compare GFCIs, "Ground Fault Circuit Interrupters", which detect when some current supplied to the device is going missing (i.e., returning through a different path involving ground) and shut things down if the missing current exceeds some level in milliamps. The main risk from a ground fault is electrocution.

It turns out that detecting arcs is hard. Really, really hard. The window between "normal operation of some random crap that's plugged in" and "bad stuff" is tiny, or even nonexistent. (Old tools with brushed motors arc during normal operation!) I worked on an arc fault detector once, as part of a larger project. We never got the thing working before the whole project got canned. It was consistently the one piece of the project that I was reporting to management as "We have no idea how to make this work. The rest of this thing, we have a plan for (maybe a bad plan, and maybe we won't execute well; such is life in R&D), but the arc detector doesn't work, we have no plan for it, and no idea how to make a plan." And we were doing a next-generation version of a device already shipping — we should have had a working arc detector right out of the gate! But it didn't work.

(The tests for arcs, incidentally, were insane. We used the test procedure from the previous-generation product, a special board made up with various "simulated arc strengths". Then we set up a low-kV range power supply, put on those giant rubber gloves that you see in cartoons, and moved in a pointy probe, by hand, toward the right spot on the test board until it arced over. This was less than reliable, and rather difficult to automate. (My proposal to automate testing by changing the intern's name to "Automated" was not accepted.) It turns out that the arc signature is deeply dependent on the exact test method you use. We had another fixture designed in-house involving a variable-distance spark gap made with two adjustable spheres. Its results were completely and totally different than the other board, so we just pretended it had never existed.)

So arc detection is difficult. It will not surprise you then to learn that the first generation of AFCI devices and breakers did not actually work correctly. They were notorious for tripping randomly and generally not things you wanted to have in your life. They were also expensive (probably paying more for the testing than for the materials cost). The NEC mandated their use anyway. Their reliability was so ridiculously poor that there was general agreement among everyone that that part of the NEC should just be ignored and standard or GFCI devices used instead. Did the NEC care? No, they insisted that AFCIs were important. Even though they didn't work. This made a lot of people start to distrust them.

We're on second or third generation AFCI devices now, and they seem to have improved a lot. They don't really false trigger anymore. But do they correctly trigger, or did they just desensitize them so they don't do anything at all? I haven't tested, and I don't want to!

It's also worth considering the risks mitigated by AFCIs. Arc faults at 120V are not really that common, and when serious arc faults do occur, they usually result in an electrical fire. Fire is certainly very bad, but I'd say it's a lot less dangerous than the nearly-instant death by electrocution that GFCIs prevent. (Note that at 240V arc faults are much more common, and up at 480V they are straight-up lethal in their own right. DO NOT FUCK WITH 480.)

So the NEC mandated AFCI devices that caused major hassle, mitigated minor risks, and cost a lot of money. That annoyed people. This came on the heels of them requiring GFCIs everywhere (same issue; ground faults in non-wet locations are not really a major risk with North American style TN-C-S earthing, but at least GFCIs work). That annoyed people. And then they had required TR receptacles everywhere (which, personally, I consider of very little benefit, though I won't argue with anyone who disagrees; at least it's obvious what's going on there), when that technology was also half baked (seriously, early TR receptacles were horrid to use, though they are pretty decent now). That annoyed people.

You can see the trend. A lot of crappy technologies were made mandatory at our expense for minor to modest gains in safety, high losses in reliability, and extreme costs in annoyance. Thus, the question: who are these guys really looking out for? Us? Manufacturers? Insurers?


> Old tools with brushed motors arc during normal operation!

I have all of my grandfathers old Craftsman steel-shell electric power tools with brushed motors. I put a new cord on one of the hand drills a few years ago (the old cloth covered cords are terrifying) and tried using it for a project. That thing throws sparks like a Zippo.


They're fun to use in dim lighting like under a cabinet. You get your own little light show!


When driving a car with internal combustion engine, you pay a lot (in Europe especially a lot!) taxes in the gas price. This means that all the people driving EV would (so far) avoid this tax and this means that this must be put to an end!!!!1

So this move might be also about taxing the EVs (just a tin-foil-hat wearing conspiracy theory maker here, don't take my words too seriously)


I don't think you have to go that far.

I think the NEC is beholden to the people who make this stuff. Right now I have a 14-50R in my garage (I don't even use it, I have it shut off at the panel; I don't have an EV, this is just new construction). The standard breaker is $18.98 right now at the big orange store. The GFCI version they're trying to make mandatory is $190.68.

I think that says all you need to know.

(And before anyone says they must cost that much more to make... they do not. I have designed GFI and AFI devices. You need to add a circuit board, yes, a pretty rugged one. The ordinary breaker is all mechanical. But that does not cost $170 more to do.)


Here in the UK, we call them RCDs or RCBOs, and they cost £18: https://www.toolstation.com/bg-compact-rcbo/p81865


Basic GFCIs are also around the same price in the US.

The discussion in the article is about mandating that weirdo breakers also contain GFCI/AFCI components. Unsurprisingly, manufacturers charge a lot more for the oddball parts.

(My load center's vendor also seems to be particularly bad with the price gouging, but I didn't exactly choose it, so in that respect it's perfectly representative of what gets chosen for people.)


That is amazing price for something that millions of will be made each year. Just calculate how many of them are needed in total and then take replacement even every 50 years or something. It scales to large number needed.


Indeed, and this mass-produced stuff is pretty simple compared to an IC chip. Who are handcrafting these devices, blonde virgin maidens at night under the shine of a full moon? :D


Don’t worry - in my country (Finland) they already thought of that and instead of the emissions based annual road tax, which would of course be zero, they managed to add a ‘tax on driving power’ to electric cars.

Notwithstanding that electricity for any use already has a per KWh tax added. Plus sales tax of course.


Well, in Italy the road tax has always been on engine power.

Indeed the VAT is a nuisance, actually the most regressive form of taxation possible: rich people with enough income who can afford to spend only a fraction of it, end up paying VAT accordingly; while low income citizens who have to spend all their salary end up with an additional, significant tax burden on their whole net income.